Home › Learn › HVAC Duct Takeoff: How to Measure Ductwork From Mechanical Plans
Part of: What Is a Takeoff in Construction? How to Do One From Plans
HVAC Duct Takeoff: How to Measure Ductwork From Mechanical Plans

An HVAC duct takeoff measures every duct run on the mechanical plans in linear feet, grouped by size and gauge, and counts the fittings, dampers and air devices that go with them. To price sheet metal, turn each size into square feet (perimeter times length) and then into pounds using the weight per square foot for that gauge.
Measure Plans in Minutes
Upload your full plan set. Get every length, area and count. Export the takeoff to Excel.
A floor plan drawing, not a photo of a room.
Plans from $9 a month. 100% money-back guarantee.
What goes into an HVAC duct takeoff?
Three kinds of quantity. Straight duct is measured in LF and kept on separate lines for each size, shape and gauge. Fittings, accessories and air devices are counted in EA. Sheet metal for fabrication is figured from the straight duct as square feet and pounds.
| Item | Unit | How you get it |
|---|---|---|
| Rectangular duct, by size and gauge | LF | Measure each run on the duct plan |
| Round and spiral duct, by diameter | LF | Measure each run on the duct plan |
| Flexible duct runouts | LF | Measure, or count runouts times a typical length |
| Elbows, transitions, branch fittings, end caps | EA | Count by type and size |
| Volume dampers, fire dampers, access doors | EA | Count from the plan and duct accessory notes |
| Diffusers, registers and grilles | EA | Count from the ceiling plan, check the air device schedule |
| Sheet metal | SF, then lb | Perimeter x LF, then x lb per SF for the gauge |
| Duct wrap or liner, if specified | SF | Start from the same perimeter x LF figure |
Galvanized steel is the most common duct material, according to the Wikipedia article on ducts, which also notes that rectangular duct most often comes in 4 ft sections and that flexible duct runs are kept short. Duct board and other materials show up too, so read the spec before assuming steel.
Which mechanical sheets and specs hold the ductwork?
The duct plans in the M series carry the layout and the size of each run. The mechanical legend tells you what each line type and symbol means, and the schedules list the air devices with their neck sizes and airflow. Keep the legend open the whole time.
Diffusers and grilles also appear on the reflected ceiling plan, which is the easiest sheet to count them from. Vertical drops, risers and offsets often show only in a section drawing or a detail, so a run that looks like 20 ft in plan can be longer once you add the drop to the ceiling.
The specification sets material, gauge and sealing. In MasterFormat, ductwork falls under Division 23, with section 23 31 13 for metal ducts and 23 33 00 for air duct accessories such as dampers. Specs often point to the SMACNA HVAC Duct Construction Standards; one owner spec for section 23 31 13 ductwork from the University of Houston is an example. Take the gauge from the job spec, not from habit.
How do you read duct sizes on a plan?
A rectangular duct marked 24x12 is 24 inches by 12 inches. On a plan view the first number is usually the side you see, which is the width, and the second is the depth into the page. Round duct is marked by diameter, often with a diameter symbol or DIA.
Not every office follows the same order, and sections sometimes flip it so the visible side still comes first. Check the legend or general notes for the convention on your set. For the perimeter math it does not matter which number comes first, but it matters for fit and for fittings.
How to calculate ductwork sheet metal by area and weight
A duct is a tube of sheet metal, so its surface area is its perimeter times its length. Unroll a 24x12 duct and you get a strip 72 inches wide: 24 + 12 + 24 + 12 = 72 inches, or 6 ft. A 10 ft piece of it is 6 x 10 = 60 SF of sheet metal.
For round duct, use the circumference: diameter x pi. An 8 inch duct is 8 x 3.1416 = 25.13 inches around, which is 25.13 / 12 = 2.094 ft. Each linear foot of it takes about 2.094 SF of metal.
To get pounds, multiply square feet by the weight per square foot for the gauge. The galvanized sheet metal gauge chart from American Steel and Aluminum lists these typical figures. The mill certificate or your supplier's spec wins if it differs.
| Galvanized gauge | Thickness (in) | Weight (lb per SF) |
|---|---|---|
| 26 | 0.0217 | 0.906 |
| 24 | 0.0276 | 1.156 |
| 22 | 0.0336 | 1.406 |
| 20 | 0.0396 | 1.656 |
| 18 | 0.0516 | 2.156 |
These weights are for flat sheet. Seams, locks, joints and scrap add metal that the perimeter math does not see, so shops carry an allowance on top. Set yours from your own fabrication history; the general method is in construction waste factors.
How to do a duct takeoff from mechanical plans, step by step
- Pull the duct plans, the mechanical legend, the air device schedule and the duct spec sections, and note the revision date.
- Set the scale on each mechanical sheet from a printed dimension or the scale bar.
- Pick one duct size and gauge, measure every straight run of it, and write the LF on its own line.
- Repeat for each size, including round duct and flex runouts.
- Check sections and details for drops, risers and offsets, and add that length to the right line.
- Count fittings, dampers and accessories by type and size in EA.
- Count diffusers, registers and grilles, and check the total against the air device schedule.
- Convert each duct line to SF and pounds, add your allowance, and total by gauge.
Decide once how you handle length through fittings. Either the LF runs stop at each fitting and the fittings are priced on their own, or the LF runs through them and the fittings carry labor only. Mixing the two on one job counts the same metal twice. Measuring the runs themselves works like any linear feet calculation, and the fitting tally follows the one-symbol-at-a-time method from the count takeoff guide.
HVAC duct takeoff example: one supply system
Say a supply system has a 24x12 trunk, one 14x10 branch and four 10x8 branches. The 14x10 branch feeds four 8 inch round runouts and each 10x8 branch feeds one, for eight runouts and eight diffusers. In this example spec the trunk is 24 gauge and everything else is 26 gauge.
| Duct | Gauge | LF | Perimeter (ft) | SF | lb per SF | lb |
|---|---|---|---|---|---|---|
| 24x12 trunk | 24 | 60 | 6.000 | 360.0 | 1.156 | 416.2 |
| 14x10 branch | 26 | 40 | 4.000 | 160.0 | 0.906 | 145.0 |
| 10x8 branches (4 x 18 LF) | 26 | 72 | 3.000 | 216.0 | 0.906 | 195.7 |
| 8 in round runouts (8 x 6 LF) | 26 | 48 | 2.094 | 100.5 | 0.906 | 91.1 |
| Total | 220 | 836.5 | 848.0 |
Line by line: the 24x12 perimeter is 72 in, or 6 ft, so 6 x 60 = 360 SF and 360 x 1.156 = 416.2 lb. The 14x10 is 48 in, or 4 ft, so 4 x 40 = 160 SF and 160 x 0.906 = 145.0 lb. The 10x8 is 36 in, or 3 ft, so 3 x 72 = 216 SF and 216 x 0.906 = 195.7 lb.
The round runouts are 2.094 x 48 = 100.5 SF, and 100.5 x 0.906 = 91.1 lb. Totals: 360 + 160 + 216 + 100.5 = 836.5 SF, and 416.2 + 145.0 + 195.7 + 91.1 = 848.0 lb.
At an example allowance of 10% for seams and scrap, 848.0 x 1.10 = 932.8 lb, so you would carry about 933 lb of galvanized. If your shop runs rectangular duct in 4 ft sections, the trunk is 60 / 4 = 15 sections, which tells you how many transverse joints to price. Use your own allowance and section length; these are only there to show the arithmetic.
The count side of the same takeoff:
| Item | Count | Where it came from |
|---|---|---|
| 24x12 90 degree elbows | 2 EA | Duct plan |
| Branch fittings off the trunk | 5 EA | 1 for the 14x10, 4 for the 10x8s |
| 8 in round runout fittings | 8 EA | One per runout |
| Volume dampers | 8 EA | One per runout, per the plan notes |
| End caps | 5 EA | One per branch end |
| Supply diffusers | 8 EA | Ceiling plan, checked against the air device schedule |
A quick sanity check: eight runouts should mean eight diffusers and eight runout fittings. If the air device schedule shows nine, a diffuser is missing from your count or the plan is missing a runout. Sort it out before you price labor.
Common ductwork takeoff mistakes
- Lumping sizes together. 60 LF of 24x12 and 60 LF of 10x8 are very different amounts of metal.
- Missing drops and risers that only show in sections or details.
- Using one gauge for the whole job when the spec changes gauge by duct size or pressure class.
- Counting fitting length in the LF and pricing the fitting again.
- Forgetting flex runouts, dampers or access doors because they are drawn small or called out in notes.
- Reading one sheet at the wrong scale. Mechanical sheets and enlarged plans can use different scales.
Several of these are the same traps every trade hits, which are covered in more depth in common takeoff mistakes. The plumbing side of a mechanical set runs the same way, piping by size in LF and fixtures by count, as shown in the plumbing takeoff guide.
How to do an HVAC duct takeoff on a PDF
On a PDF set the scale once per sheet and click along each run instead of rolling a scale ruler across paper. In MeasureFloorPlan, every sheet of a multi-page PDF is part of one plan and each sheet keeps its own scale, which helps when the enlarged mechanical room is drawn at a different scale than the floor.
The Distance tool gives you linear feet, and you can group runs into named line items with subtotals, such as one item for 24x12 and one for 10x8. In Takeoff mode the Count tool (keyboard shortcut C) takes one click per item, and the Other category takes a custom name like diffusers or volume dampers. Lengths and counts go out in the CSV, Copy table and PDF exports, so the SF and pound math can live in your own spreadsheet.
It measures lengths, areas and counts. It does not do plan markups or assembly-based estimating. For a look at what it covers by trade, see takeoff software for contractors. There is a free demo on a sample plan; Starter is $9 a month for 3 plans and Pro is $29 a month unlimited, with a 48-hour money-back guarantee. Outside work on the same project, such as sod and planting beds, is measured the same way on the site plan; see the landscape takeoff guide.
Measure Plans in Minutes
Upload your full plan set. Get every length, area and count. Export the takeoff to Excel.
A floor plan drawing, not a photo of a room.
Plans from $9 a month. 100% money-back guarantee.
Frequently Asked Questions
What is a duct takeoff?
In estimating, it is the measured list of ductwork on a job: straight duct in linear feet by size, fittings and accessories counted by type, and sheet metal converted to square feet and pounds. The same word also names the branch fitting that connects a branch duct to a main, and on an estimate you count those fittings like any other.
How do you calculate ductwork weight?
Find the perimeter of the duct, multiply it by the length to get square feet of sheet metal, then multiply by the weight per square foot for the gauge. A 24 x 12 duct has a 6 ft perimeter, so 60 LF is 360 SF, and at 1.156 lb per SF for 24 gauge galvanized that is about 416 lb.
How do you calculate round duct weight?
Use the circumference instead of the perimeter: diameter times pi. An 8 inch round duct has a circumference of about 25.13 inches, or 2.094 ft, so 48 LF is about 100.5 SF. At 0.906 lb per SF for 26 gauge galvanized, that is about 91 lb.
How do you measure ductwork from plans?
Set the scale for the mechanical sheet, then measure each straight run of one size at a time and write it on its own line with the size and gauge. Count fittings, dampers and air devices separately in EA, and check sections or details for vertical drops the plan view does not show.
How do you set up an HVAC duct quantity takeoff in Excel?
Use one row per duct size and gauge with columns for LF, perimeter in feet, square feet, pounds per square foot and total pounds. Put fittings and accessories in a second block counted in EA. Keep the formula visible in each row so a reviewer can follow the math.